logo
Goede prijs.  online

details van de producten

Created with Pixso. Huis Created with Pixso. Producten Created with Pixso.
Waterkwaliteitscontroleur
Created with Pixso.

Explosion-proof Integrated Ultrasonic Level Meter

Explosion-proof Integrated Ultrasonic Level Meter

Merknaam: JUGE
Modelnummer: AG2087
Moq: 1 eenheid
Prijs: USD100-500
Verpakking: Neutraal karton
Betalingsvoorwaarden: Online bestelling, T/T
Gedetailleerde informatie
Plaats van herkomst:
Nanjing, China
Certificering:
IOS9001, CE
Naam:
Explosieveilige geïntegreerde ultrasone niveaumeter
Bereik:
0-15m
Levering vermogen:
100 eenheden/week
Markeren:

explosion-proof ultrasonic level meter

,

integrated water level controller

,

ultrasonic water quality meter

Productbeschrijving

Explosion-proof Integrated Ultrasonic Level Meter


>>Overview
The instrument's probe emits a signal wave that reflects off the liquid surface and returns to the probe. After receiving the reflected signal, the probe calculates the time between transmission and reception to determine the measured distance L. The current liquid level H is obtained by subtracting the measured distance L from the instrument's mounting height TH.


The ‌instrument range‌ refers to the maximum distance the instrument can measure. The mounting height TH must be less than this range.


The ‌instrument dead zone‌ is the area near the probe where measurement is impossible. The distance between the highest liquid level and the probe must exceed the dead zone.


For example, with a dead zone of 0.5 m, the distance from the highest liquid level to the probe must be greater than 0.5 m.

Example: Range: 6 m, Dead zone: 0.45 m → Effective measurement range: 0 to 5.55 m.


Signal emission from the probe is a divergent process (characterized by a beam angle). Installation must account for this angle to prevent the signal from striking protrusions on tank walls or channel edges.


>>Technical Parameter

Measuring Range 0-15m (Selectable based on actual range; customizable)
Resolution 1mm
Dead Zone 0.45~0.6m
Accuracy ±0.25 (under standard conditions)
Pressure ≤400 kPa (4 atm)
Display LCD
Analog Output 4-20mA
Power Supply 24VDC
Protection Class IP65
Ambient Temp. -20°C to 60°C